Fume Hood Face Velocity and CFM Explained

AirGuard Pro benchtop fume hood with the sash at the 18 inch stop, on steel base cabinets

Two numbers come up in every fume hood conversation: face velocity and CFM. Your mechanical engineer needs them to size ductwork and the blower, your facilities team needs them to plan makeup air, and your safety officer uses them to check that the hood protects people. Here is what they mean and how they work together.

What is face velocity?

Face velocity is the average speed of air moving into the fume hood opening, measured in feet per minute (fpm). It is what keeps fumes inside the hood and away from the person working at it.

Many labs design around 100 fpm, and a range of roughly 80 to 120 fpm is common in lab ventilation guidelines. Faster is not always better. Very high face velocities create turbulence around the user's body that can actually pull fumes out of the hood. Too low, and drafts in the room can overcome the airflow. Your facility's chemical hygiene plan or safety officer sets the target for your lab.

What is CFM?

CFM, cubic feet per minute, is the volume of air the hood exhausts. It determines the size of the ductwork and blower, and how much heated or cooled makeup air the room needs.

How to calculate CFM

The basic formula is:

CFM = face velocity (fpm) x open area of the sash (square feet)

For example, a 48" AirGuard Pro has a 40" wide opening. With the sash at 18":

  • Open area: 40" x 18" = 720 square inches = 5.0 square feet
  • CFM at 100 fpm: 5.0 x 100 = 500 CFM

Fume hood CFM calculation: a 40 by 18 inch sash opening is 5.0 square feet, times 100 feet per minute equals 500 CFM

AirGuard Pro exhaust by size

Hood width Opening width CFM at 18" sash Static pressure
48" 40" 500 0.35"
60" 52" 650 0.35"
72" 64" 800 0.35"
96" 88" 1,100 0.35"

CFM calculated at 100 fpm at the 18" working sash height. Static pressure is the resistance of the hood itself, which your engineer adds to the ductwork losses when selecting a blower.

Why sash height matters

Because CFM depends on the open area, the sash height you plan for drives the whole exhaust system. Many hoods, including ours, have a sash stop at 18". If users work with the sash at the stop, the system can be designed for the 18" figure. If the sash will regularly be raised higher, the system has to handle the larger opening. Agree on a design sash height with your engineer and safety officer, and train users to work with the sash at that height or lower.

Bypass hoods and lower face velocities

In a bypass hood, an opening above the sash lets air keep flowing as the sash closes. The exhaust volume stays fairly constant, and the face velocity doesn't spike to high levels when the sash is nearly closed. The AirGuard Pro is a bypass hood that supports performance down to 60 fpm. Where your safety program allows a lower design face velocity, that means less air to exhaust and condition. At 60 fpm, the 48" hood at an 18" sash needs about 300 CFM instead of 500.

Bypass fume hood airflow with the sash closed and open: air enters through the bypass above the sash and through the airfoil

Makeup air: the hidden cost

Every cubic foot a hood exhausts must be replaced with outside air that is heated or cooled. That is why fume hoods are among the largest energy users in a lab building. To keep costs down:

  • Buy the hood width you need, not the largest that fits.
  • Design for a realistic sash height and keep sashes closed when the hood isn't in use.
  • Work with your engineer on the lowest face velocity your safety program accepts.

Checking face velocity

After installation, a qualified technician should measure face velocity with a calibrated anemometer, taking readings on a grid across the sash opening and averaging them. ASHRAE 110 testing goes further, using tracer gas to check how well the hood contains fumes. An airflow monitor, like the AFA 500 included on every LabSpace hood, then alerts users if airflow drops during daily use.

Learn more

See our benchtop fume hood buyer's guide and installation checklist, or download cut sheets and manuals from Resources. Questions about sizing? Call 616-407-0252.